News  |  About Us  |  Contact Us

    Our Brands

    EJB Series Explosionproof Enclosures

    Brand: Crouse Hinds

    EJBs are used in hazardous areas:

    • As a junction or pull box
    • To provide enclosures for splices and branch circuit taps
    • For housing terminal blocks, relays and other electrical devices
    • In areas which are hazardous due to the presence of hydrogen or gases and vapors of equivalent hazard such as found in process industries, missile bases and gas manufacturing plants
    Product DetailsFeaturesCertifications
    • Styles: Style C or Style D
    • Conduit Sizes: 1/2"; 3/4"; 1"; 1 1/4"; 1 1/2"; 2"; 2 1/2"; 3"; 3 1/2"; 4"; 5"; 6"
    • Body and Cover Material: Copper-free aluminum (suffix -SA items and all Style C); Feraloy® iron alloy (Style D)
    • Gasket Material: Neoprene
    • Cover Bolt Material: Stainless steel (Style C); Steel (Style D)
    • Hinge Material: Stainless steel
    • Style C boxes provided with aluminum plate cover as standard, allowing for field addition of cover device holes
    • Stainless steel cover bolts (Style C only)
    • Ground joint cover opening provides maximum opening for pulling wires or mounting equipment
    • Walls of bodies may be drilled and tapped for conduit entries as shown in listings
    • Stud bolts in diagonally opposite corners of body aid in aligning cover to body during installation (not furnished with hinged covers)
    • All Style C bodies are provided with captive, triple-lead, quick-release hex head stainless steel bolts with spring loaded action which provides clear indication that cover bolts are fully retracted from the body
    • External flange design – wide unobstructed cover opening provides a completely accessible interior for wiring and electrical equipment
    • Square corners of enclosure body provide maximum interior space and area for conduit openings
    • Internal grounding lug provides a means to ground enclosed equipment
    • Special neoprene cover gasket provides a watertight seal to meet NEMA 4 requirements, and provides superior protection for enclosed equipment against water/corrosion
    • Enclosures are machined for field installed mounting plates
    • Detachable mounting feet provide mounting flexibility; no need to replace enclosure if mounting feet are broken
    • Optional stainless steel hinges provide convenient and easy access for inspection, maintenance and systems changes
    • Enclosures are machined to accept field installed hinges
    • IEC rated when ordered with ATEX suffix
    • NEC/CEC:
    Class I, Divisions 1 and 2, Groups B*, C† and D‡
    Class II, Division 1, Groups E, F and G
    Class II, Division 2, Groups F and G
    Class III
    Class I, Zones 1 and 2
    • UL Standard: 1203
    • cUL to CSA Standard C22.2 No. 30
    • ATEX: Ex d IIB + H2 T6, IP66
    • ATEX certificate: PTB 01 ATEX 1020 U
    • Enclosure Type 3, 3R, 4, 4X*, 7BCD, 9EFG
    • IEC Standard: EN:60079-0 and EN:60079-1